Listed in Category: CPR - PVC Cables

H07V2-K

H07V2-K-Ascable-Recael-Cable-Energia-CPR11
Cable flexibleBajo en halogenosNo propagación de la llamaResistente a altas temperaturasCPR_LOGO

Applicable Standard: EN 50525-2-31

Description

Single core non-sheathed electric cables with PVC insulation. Construction according to EN 50525-2-31.

Application

For wiring indoor protected permanent fixtures, electrical equipment and fixed lights.  Suitable for energy transportation and for electric connection in fixed installations.

For more detailed information, check the EN 50565 Usage Guide for Cables with a Rated Voltage not Exceeding 450/750 V (U0 /U).

  • Operating voltage: 450 / 750 V
  • Test voltage: 2.500 V
  • Operating temperature: from -15 to 90 ºC

Section (sq.mm.)

Outer Ø aprox. (mm) Weight (kg/km) Resistance  at 20ºC(Ω/km)
1×1,5 2,9 18,9

13,3

1×2,5

3,6 30,9 7,98
1×4 4,2 44,5

4,95

1×6

4,8 62,1 3,3
1×10 6,25 105,9

1,91

1×16

7,2 157,4 1,21
1×25 9,2 242,8

0,78

1×35

10,2 333,4

0,554

  • Conductor: Flexible bare copper class 5 according to UNE EN 60228
  • Insulation: PVC type TI 3 according to UNE EN 50363-3
NPS (Cone) eurocono Box box
Drum bobina Coil rollo
100m/200m Box caja Nubox nubox
Products certified by AENOR <HAR>:

DOP (Declaration of performance) CPR: