ASCABLE - Cat.: CPR - Halogen Free Cables, Energy - Sec.:Construction, Industry
Applicable Standard: EN 50525-3-31
Cables of rated voltages up to and including 450/750 V and having thermoplastic insulation. Single core cables, resistant to flame propagation, insulated with halogen−free thermoplastic compound, for fixed wiring.
Installation in conduits, fixed on surfaces or embedded or in closed analogue systems, particular indicated for situation in which it is necessary to reduce the emission of corrosive smoke and gases, for example in case of fire. In busy oublic places like hospitals, cinemas, schools, etc.
For more detailed information, check the EN 50565 Usage Guide for Cables with a Rated Voltage not Exceeding 450/750 V (U0 /U).
Section (sq.mm.) | Outer Ø aprox. (mm) | Weight (kg/km) | Resistance at 20ºC (Ω/km) |
1×1.5 | 2.9 | 21.2 | 12.1 |
1×2.5 | 3.6 | 34.1 | 7.41 |
1×4 | 4.2 | 49.1 | 4.61 |
1×6 | 4.8 | 67.2 | 3.08 |
1×10 | 6.25 | 110.9 | 1.83 |
1×16 | 7.2 | 166.1 | 1.15 |
1×25 | 8.4 | 260.7 | 0.727 |
1×35 | 9.6 | 356.5 | 0.524 |
1×50 | 12.2 | 500.3 | 0.387 |
1×70 | 14.5 | 715.9 | 0.268 |
1×95 | 16.0 | 921.9 | 0.193 |
1×120 | 17.9 | 1167.1 | 0.153 |