Listed in Category: CPR - Halogen Free Cables

PIROFREN SOZ1-K (AS+) PH120

SOZ1-K
Cable flexibleIcona Hal Free2No propagación del incendioNo propagación de la llamaNula emisión de gases corrosivos (UNE EN 50267-2-3)Baja emisión de humos opacos (UNE EN 61034)Resistente al fuegoResistente a altas temperaturasCompatibilidad frente a los ruidos eléctricosCPR_LOGO

Applicable Standard: UNE 211025

Description

Cable consisting of polished copper stranded conductors, insulated with crosslinked elastomer, shielded with aluminum and polyester tape and tinned copper drain, with outer sheath of thermoplastic polyolefin.

Application

Appropiate for all those installations in which the integrity of the circuits has to be kept, even though they may be affected by fire.

  • Operating voltage: 300 / 500 V
  • Test voltage: 2.000 V
  • Operating temperature: from -15 to 90 ºC
Sección
mm²
Resistencia
Ω/km a 20ºC
Capacidad
pF/m
Diámetro ext.
mm
Peso
Kg/km
2×1 19,5 130 6,70 60
2×1,5 13,3 150 7,70 75
2×2,5 7,98 180 8,90 105
2×4 4,95 180 10,30 145
3×1 19,5 N/A 7,10 75
3×1,5 13,3 N/A 8,20 95
3×2,5 7,98 N/A 9,50 140
3×4 4,95 N/A 11,00 195
3×6 3,30 N/A 12,40 260
4×1 19,5 N/A 7,80 90
4×1,5 13,3 N/A 9,00 120
4×2,5 7,98 N/A 10,30 175
4×4 4,95 N/A 12,00 245
4×6 3,30 N/A 13,60 330
  • Conductor: Flexible bare copper class 5 according to UNE EN 60228
  • Insulation: Crosslinked elastomer type EI 2 according to UNE EN 50363-1
  • Arrangement of conductors: Cores stranded in layers
  • Shield: Aluminium/polyester + drain Cu Sn
  • Outer sheath: Polyolefin TM7 according to EN 50363-8
  • Usual color: Red
  • Color code:
    Formation of 2 cores: Red and Black
    Formation > 2 cores: s/HD 308 S2
Drum bobina Coil rollo
Nubox nubox
DOP (Declaration of performance) CPR:

Other denominations: