ASCABLE - Cat.: Energy, Special Cables - Sec.:Renewable Energy
Applicable Standard: EN 50618
Cables with insulation and outer sheath of cross-linked elastomer compound. Manufactured according to EN 50618 “Electrical Cables for photovoltaic systems”
For photovoltaic installations, either internal (trays, pipes, tracking systems) or external, where the cable is exposed to the weather, for example, solar parks, panels on buildings, solar tracking systems, solar mobile installations (without mechanical stress outside the facility itself ), etc.
Section sq.mm. |
Resistance (Max. at 20ºC)Ω/Km | Insulation Resistance | Max. Ampacity (Type of installation) | Ø Exterior sq.mm.(Aprox.) | |||
20º CMΩxkm | 90º CMΩxkm | 1 Cable in the air | 1 Cable onto surface | 2 Cables loaded onto surface | |||
A | A | A | |||||
1 x 1,5 | 13,7 | > 860 | > 0,86 | 30 | 29 | 24 | 4,60 |
1 x 2,5 | 8,21 | > 690 | > 0,69 | 41 | 39 | 33 | 5,00 |
1 x 4 | 5,09 | > 580 | > 0,58 | 55 | 52 | 44 | 5,60 |
1 x 6 | 3,39 | > 500 | > 0,50 | 70 | 67 | 57 | 6,40 |
1 x 10 | 1,95 | > 420 | > 0,42 | 98 | 93 | 79 | 7,05 |
1 x 16 | 1,24 | > 340 | > 0,34 | 132 | 125 | 107 | 8,70 |
1 x 25 | 0,795 | > 340 | > 0,34 | 176 | 167 | 142 | 10,40 |
1 x 35 | 0,565 | > 290 | > 0,29 | 218 | 207 | 176 | 11,80 |
Room temperature 60 C°, max. conductor temperature 120ºC |
Correction factors for different temperatures of 60 C°
Room Temperature (C°) | Correction Factors | For grouped cableways ampacity reduction factors should be applied in accordance with table B.52.17 del HD 60364-5-52. |
Until 60 | 1 | |
70 | 0,92 | |
80 | 0,84 | |
90 | 0,75 |