Listed in Category: CPR - PVC Cables

YSLCY CPR

YSLCY-JZ
Cable flexibleBajo en halogenosNo propagación de la llamaResistente a los rayos UVResistente a la absorción del aguaCompatibilidad frente a los ruidos eléctricosCPR_LOGO

Applicable Standard: EN 50525-2-11

Description

Shielded flexible cable of command and control with PVC insulation and sheath.

Application

To maneuver and control automation and interconnection between box and machinery including machine tools, air conditioning systems, industrial plants, etc.. Installation in dry, damp or wet locations, where required some resistance to grease and oil where protection against electrical interference and EMC is required. For flexible use of average level of mechanical stress with free movement without tensile or forced movements.

  • Operating voltage: 300 / 500 V
  • Test voltage: 3.000 V
  • Operating temperature:
    • Mobile Service: -15 a +70 ºC
    • Fixed Service: -30 a +80ºC

SQUARE

(Nominal)

0,50 sq.mm. SQUARE(Nominal) 0,75 sq.mm. SQUARE(Nominal) 1 sq.mm.
Nº Cores. RESISTANCE(Max. to 20 ºC)

W/km

Ø OUTER(approx.)

mm

Nº Cores. RESISTANCE(Max. to 20 ºC)

W/km

Ø OUTER(approx.)

mm

Nº Cores. RESISTANCE(Max. to 20 ºC)

W/km

Ø OUTER(approx.)

mm

2 39 5,6 2 26 6 2 19,5 6,5
3 5,9 3 6,3 3 6,8
4 6,3 4 6,8 4 7,6
5 6,8 5 7,5 5 8,2
6 / 7 7,5 6 / 7 8,1 6 / 7 9
8 8,3 8 9,2 8 9,9
10 9,4 10 10,4 10 11,3
12 9,7 12 10,7 12 11,8
14 10,1 14 11,2 14 12,4
16 10,8 16 11,9 16 13
18 / 19 11,3 18 / 19 12,5 18 / 19 13,8
20 / 21 12,3 20 / 21 13,6 20 / 21 15
24 13,4 24 14,8 24 16,4
25 / 27 13,7 25 / 27 15,1 25 / 27 16,7
30 14,1 30 15,6 30 17,3
32 / 33 14,8 32 / 33 16,3 32 / 33 18,1
36 / 37 15,3 36 / 37 16,9 36 / 37 18,7
40 16,3 40 18 40 19,8
44 17,2 44 19,2 44 21,2
48 17,7 48 19,5 48 21,5
52 18,1 52 20 52 22,3
56 18,6 56 20,7 56 22,9
60 / 61 19,3 60 / 61 21,3 60 / 61 23,7

 

SQUARE(Nominal) 1,5 sq.mm. SQUARE(Nominal) 2,5 sq.mm. SQUARE(Nominal) 4 sq.mm.
Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm
2 13,3 7,1 2 7,98 8,5 2 4,95 9,7
3 7,7 3 9,2 3 10,4
4 8,3 4 9,9 4 11,3
5 9,2 5 11,1 5 12,6
6 / 7 9,9 6 / 7 12,2 6 / 7 13,8
8 11,2 8 13,8 8 15,6
10 12,7 10 15,6 10 18
12 13,3 12 16,3 12 18,5
14 13,9 14 17 14 19,6
16 14,9 16 18,1 16 20,9
18 / 19 15,6 18 / 19 19,2 18 / 19 22,1
20 / 21 16,9 20 / 21 20,8 20 / 21 23,9
24 18,4 24 22,6 24 26
25 / 27 18,8 25 / 27 23,1 25 / 27 26,7
30 19,6 30 24,1 30 27,9
32 / 33 20,5 32 / 33 25,2 32 / 33 29
36 / 37 21,2 36 / 37 26,1 36 / 37 30,2
40 22,5 40 27,9 40 31,8
44 24 44 29,7 44 33,7
48 24,4 48 30,2 48 34,2
52 25,2 52 30,9 52 35,1
56 25,9 56 31,8 56 36,2
60 / 61 26,8 60 / 61 32,7 60 / 61 37,2

 

SQUARE(Nominal) 6 sq.mm. SQUARE(Nominal) 10 sq.mm. SQUARE(Nominal) 16 sq.mm.
Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm
2×6 3,3 11,4 2×10 1,91 15 2×16 1,91 18,3
3×6 12,2 3×10 15,8 3×16 19,6
4×6 13,5 4×10 17,7 4×16 21,6
5×6 14,9 5×10 19,5 5×16 24
7×6 16,4 7×10 21,4 7×16 26,6

 

SQUARE(Nominal) 25 sq.mm. SQUARE(Nominal) 35 sq.mm.  
Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm Nº Cores. RESISTANCE(Max. to 20 ºC)W/km Ø OUTER(approx.)mm      
2×25 0,78 22,1 2×35 0,554 24,9
3×25 23,6 3×35 26,6
4×25 26 4×35 29,5
5×25 29,2 5×35 32,4
7×25 31,8 7×35 35,4
  • Conductor: Flexible bare copper class 5 according to EN 60228
  • Insulation: PVC type TI2 improved according to EN 50363-3
  • Colour code:
    • Type J: Numerated black with GN/YE (Earth)
    • Type O: Numerated black without GN/YE (Earth)
    • Type JB: Colors with GN/YE (Earth)
    • Type OB: Colors without GN/YE (Earth)
  • Wire disposition: Concentique layers
  • Separator: Polyester tape
  • Shield: Tinned copper braid. Physical coverage: > 85%
  • Outer cover: PVC type TM2 according to EN 50363-4-1
  • Average colour: Gray
Drum bobina Coil rollo
DdP/DoP (Declaration of performance) CPR:

 Other denominations: