Listed in Category: CPR - PVC Cables

RTAP CPR

RTAP - CPR
Cable flexibleBajo en halogenosNo propagación de la llamaCompatibilidad frente a los ruidos eléctricosCPR_LOGO

Description

Shielded cable for intercom and security. Cable made of flexible copper conductors insulated in PVC, wired conductors, shielded to the assembly with aluminum / polyester tape plus tinned copper drain and an outer PVC cover.

Application

For security systems (alarms) and telephony and intercomunication devices where protection against electrical noises is required.

Note: Not suitable for direct connection to the electric power supply or other sources of low impedance.

  • Operating voltage: 250 V
  • Test voltage: 1.000 V
  • Operating temperature: from -15 to +70 ºC
  • Capacity between conductors: 120 ± 15%
0,20 mm² 0,22 mm² 0,25 mm² 0,5 mm² 0,75 mm²
Resistance at 20 ºC (Ω/Km) 108,0 88,6 79,0 39,0 26,0
Number of conductors 0,20 mm² 0,22 mm² 0,25 mm² 0,5 mm² 0,75 mm²
2 2,9 3,1 3,2 4,2 4,8
3 3,1 3,3 3,4 4,5 5,1
4 3,4 3,6 3,7 4,9 5,6
5 3,7 4,0 4,1 5,6 6,4
6 4,0 4,3 4,4 6,0 6,9
8 4,5 5,0 5,2 6,8 7,8
10 5,4 5,8 6,0 7,6 9,0
12 5,6 6,0 6,2 8,1 9,3
14 5,9 6,3 6,5 8,5 10,0
16 6,2 6,9 7,1 9,0 10,6
19 6,7 7,2 7,6 9,4 11,3
21 7,2 7,7 8,4 10,4 12,2
24 7,7 8,3 8,6 11,2 13,2
  • Conductor: Flexible bare copper according to UNE EN 13602
  • Insulation: PVC type TI 52 according to UNE EN 50290-2-21
  • Arrangement of the conductors: Cores stranded in layers
  • Screen: Aluminium/polyester tape + Cu Sn drain wire
  • Outer sheat: PVC type TM 52 according to UNE EN 50290-2-22
  • Usual color: White
  • Color code: Table 3
Drum bobina Coil rollo
Nubox nubox
DOP (Declaration of performance) CPR:

Other denominations: