Listed in Category: CPR - PVC Cables

H07RN-F CPR

H07RN-F
Cable flexibleBajo en halogenosNo propagación de la llamaResistente a grasas y aceitesResistente a los rayos UVCPR_LOGO

ASCABLE - Cat.: , - Sec.:, ,

Applicable Standard: EN 50525-2-31

Description

Flexible cable, with insulation and covered with rubber for mobile service, for interior and exterior use.

Application

In industrial and agricultural workshops, buildings, for applications and powering of apparatus, for demanding services where the cables are subject to average mechanical stress (examples: heating plates, portable lamps, electrical equipment such as drills, circular saws and household electric tools). In dry, humid and wet locations. In fixed installations, for example, on plaster in provisional buildings and barracks or refuges for storage.

For more detailed information, check the EN 50565 Usage Guide for Cables with a Rated Voltage not Exceeding 450/750 V (U0 /U).

  • Operating voltage: 450 / 750 V
  • Test voltage: 2.500 V
  • Operating temperature: from -35 to 60ºC
Section
(sq.mm.)
Resistance
(Ω/km to 20º C)
Diameter
(mm)
Weigth
(kg/km)
1×1,5 13,3 5,9 55
1×2,5 7,98 6,5 70
1×4 4,95 7,5 95
1×6 3,3 8,4 125
1×10 1,91 10,2 190
1×16 1,21 11,4 255
1×25 0,780 13,2 365
1×35 0,554 14,7 480
1×50 0,386 16,9 660
1×70 0,272 19,2 890
1×95 0,206 21,6 1150
1×120 0,161 23,8 1430
1×150 0,129 26,0 1750
1×185 0,106 28,3 2110
1×240 0,0801 31,8 2730
2 x 1 19,5 8,4 90
2 x 1,5 13,3 9,1 109
2 x 2,5 7,98 10,8 158
2 x 4 4,95 12,4 217
2 x 6 3,3 13,8 282
2 x 10 1,91 19,4 539
2 x 16 1,21 21,8 722
2 x 25 0,780 25,9 1043
3 x 1 19,5 9,1 110
3 x 1,5 13,3 9,8 134
3 x 2,5 7,98 11,6 196
3 x 4 4,95 13,3 271
3 x 6 3,3 14,8 355
3 x 10 1,91 20,7 674
3 x 16 1,21 23,3 913
3 x 25 0,780 27,7 1324
3 x 35 0,554 30,9 1754
3 x 50 0,386 35,8 2409
3 x 70 0,272 40,5 3211
3 x 95 0,206 45,1 4210
4 x 1 19,5 10 136
4 x 1,5 13,3 10,8 166/td>
4 x 2,5 7,98 12,7 241/td>
4 x 4 4,95 14,6 336/td>
4 x 6 3,3 16,4 449
4 x 10 1,91 22,6 833
4 x 16 1,21 25,4 1138
4 x 25 0,780 30,7 1714
4 x 35 0,554 34,2 2204
4 x 50 0,386 39,6 3029
4 x 70 0,272 44,9 4121
4 x 95 0,206 50,4 5361
5 x 1,5 13,3 11,8 206
5 x 2,5 7,98 14 297
5 x 4 4,95 16,3 422
5 x 6 3,3 18 567
5 x 10 1,91 24,8 1010
5 x 16 1,21 28 1400
5 x 25 0,780 33,6 2096
5 x 35 0,554 39,5 2700
5 x 50 0,386 44,2 3730
7 x 2,5 7,98 17,1 448
12 x 1,5 13,3 20,0 530
12 x 2,5 7,98 23,4 720
24 x 1,5 13,3 27,5 960
24 x 2,5 7,98 32,6 1350
  • Conductor: Flexible bare copper class 5 according to UNE 60228
  • Insulation: Rubber compound, type EI4 according to EN 50363-1
  • Arrangement of the conductors: Cores stranded in layers
  • Outer sheath: Rubber compound, type EM2 according to EN 50363-2-1
  • Usual color: Black
  • Color code: Table 2
  • Note: In single core, the insulation color is black.

Drum bobina Coil rollo
Products certified by:

DOP (Declaration of performance) CPR: