Listed in Category: CPR - PVC Cables

DATALF RC4V-K V-500

DATALF RC4V-K
Cable flexibleBajo en halogenosNo propagación de la llamaResistente a los rayos UVResistente a grasas y aceitesCompatibilidad frente a los ruidos eléctricosResistente a altas temperaturasCPR_LOGO

Description

Flexible shielded cables for instrumentation and control. According to standard EN 50288-7.

Application

Instrumentation and controlcable for signaling and measuring in areas with great levels of interference due to electric and electromagnetic fields.

  • Operating voltage: 300 / 500 V
  • Test voltage: 2.000 V
  • Operating temperature: from -15 to +90 ºC
1 mm² 1,5 mm² 2,5 mm² 4 mm²

6 mm²

Resistance at 20 ºC (Ω/Km)

19,5 13,3 7,98 4,95 3,3
Number of conductors 1 mm² 1,5 mm² 2,5 mm² 4 mm²

6 mm²

2

6,6 7,2 8,6 9,8 11,2
3 6,9 7,8 9,3 10,6

12,0

4

7,7 8,5 10,1 11,5 13,6
5 8,4 9,4 11,2 13,0

15,0

6 / 7

9,3 10,4 12,5
8 10,5 11,9 14,1

10

12,0 13,5 16,6
12 12,4 13,9 17,1

14

13,0 14,9 18,1
16 13,9 15,8 19,2

19

14,9 16,8 20,2
21 16,3 18,2 22,0

24

17,8 19,8 24,0
27 18,1 20,2 24,5

  • Conductor: Flexible bare copper class 5 according to EN 60228
  • Insulation: Crosslinked polyethylene according to EN 50290-2-29
  • Arrangement of conductors: Cores stranded in layers
  • Screen: Bare copper braid. 60% coverage.
  • Outer sheath: PVC type TM51 according to EN 50290-2-22
  • Usual colour: Black
  • Colour code: Table 2
Drum bobina Coil rollo
DOP (Declaration of performance) CPR:

Other denominations: