Listed in Category: Communication

EIB BUS / KNX

EIB-BUS-ZH-CPR
Cable flexibleIcona Hal Free2No propagación de la llamaNo propagación del incendioNula emisión de gases corrosivos (UNE EN 50267-2-3)Baja emisión de humos opacos (UNE EN 61034)CPR_LOGO

Description

Shielded cable with LSZH Polyolefin oversheath, based in standard UNE 212016.

Application

Electrical installation cable designed to control building automation systems: building management, energy management, system timing, decentralized control of lights, heat, air conditioning, ventilation, blinds, locks, electronic signage, etc. Aligns with EIB (European Installation Bus) and KNX systems.

  • Temperature range: -15 a +70 ºC
  • Electrical resistance of the conductor at 20º C: < 36 Ω/km
  • Electrical insulation resistance at 20º C: > 1.000 MΩxKm
  • Capacitance pair to 1 KHz: 50 ± 10 pF/m
  • Characteristic impedance (Zo): 100 Ω
  • Nominal voltage A.C.: ≤ 250 V
  • Nominal voltage D.C.: ≤ 300 V
  • Test voltage: 1.000 V
Type (pairs per section) / sq.mm. Ø Ex. sq.mm.
1x2x0,50 5 ± 0,3
2x2x0,50 6,6 ± 0,3
  • Conductor: Rigid bare copper class I according to EN 60228
  • Insulation: Polyethylene Type ADPE according to EN 50290-2-23
  • Formation:
    • 1 Pair: Cores twisted / Colour: Red-Black
    • 2 Pairs: Twisted in STAR QUAD / Colour Pair 1: Red-Black / Pair 2: White-Yellow
  • Shield: Cu Sn Drain wire + Aluminium/polyester tape
  • Outer Sheath: LSZH thermoplastic Polyolefin according to EN 50290-2-27

 

Drum bobina Coil rollo
Nubox nubox
DdP/DoP (Declaration of performance) CPR:

 Other denominations: